Our critical power products and services including Uninterruptible Power Supply Systems lead the way in providing professional solutions for our customersβ power needs. As an industry leader, we offer both new and refurbished power and electrical equipment in order to surpass our customersβ expectations.
Questions about our UPS Power Systems? Give us a call. Experts are standing by: 1-877-779-6464.
Search Department
Search Category
Search Subcategory
Input
Voltage 208, 240, 480 or 600 VAC, 60 Hz,
3 or 4-Wire plus ground
Voltage Range +10%, -25%
Frequency Range 60 Hz ± 5%
Current Limit 125% of full load
input current
Current Walk-In 20 seconds to full load
Surge Protection Sustains input surges
without damage, per criteria listed in ANSI
C62.41-1980 (IEEE 587)
Output
Voltage 208, 240, 480 or 600 VAC, 60 Hz,
3 or 4-Wire plus ground
Voltage Regulation ±1% for balanced load
Voltage Unbalance ±1% for balanced load,
±2% for 50% unbalanced load, ±5% for 100%
unbalanced load
Voltage Adjustment Range ±5%
Frequency Regulation 60 Hz ±0.1%
Load Power Factor Range 0.9 Leading
to 0.5 Lagging
Power Rating Rated kVA at 0.8 lagging
power factor
Harmonic Distortion 5% maximum
total for linear loads. 3% maximum for
single harmonics
Phase Displacement 120° ±1° for balanced
load. 120° ±3° for unbalanced load.
Transient Response ±1% for loss or return of input power. ±4%
for 20% step load or a manual transfer of 100% load. ±5% for 30%
step load. ±8% for 50% step load.
Transient Recovery Time To within 1% of output voltage within
50 milliseconds
Overload Capability 125% for 10 minutes. 150% for 30 seconds.
Fault Clearing Current 300% subcycle
Environmental
Operating Temperature 32-104° F (0-40° C) for UPS;
68-86° F (20-30° C) for battery
Non-Operating Temperature -4°F to 158°F (-20°C to 70°C)
For battery, check manufacturers recommendations
Relative Humidity 0 to 95% non-condensing
Altitude Up to 2000 meters. Derated for higher elevations
Audible Noise Level 65 dBA measured at 1 meter from the UPS
Physical
Cabinet NEMA Type 1 freestanding. Provided with casters
and leveling feet.
Cooling Forced air. Redundant fans
Cable Entry Top or bottom
Access Front access only